BFI-E3-32-0153-1F4A-MTP
Article number 63515-MTP
- Output power 4.0 kW
- Output 3x230 VAC, 15,3 A
- Input voltage 1x200-240 VAC
- IP66
Facts
General description
Article number | 63515-MTP |
Warranty | 2 year |
Mechanical
IP class | IP66 |
Physical size | Size 3 |
Measurements (H x W x D) | 310 mm x 211 mm x 235 mm |
Weight | 6.6 kg |
Typical power loss at rated power | 0,02 |
Main switch | No |
Built in Main switch, control switch and potentiometer | No |
Conformal coated PCBs | Yes, 3C3/3S3 conformal coated PCBs |
Output ratings
Output voltage | 3 x 230 VAC |
Rated motor current | 15.3 A |
Overload capacity | 150% for 60 seconds, 175% for 2,5 seconds |
Motor power | 4.0 kW |
Output frequency | 0 – 500Hz, 0.1Hz resolution |
Built-in brake transistor | Yes |
Regenerative capacity | 100 % ED |
Input ratings
Supply voltage | 200 – 240VAC ± 10% |
Voltage fluctuations | +/- 10% |
Phase imbalance | 3% maximum allowed |
Displacement factor | > 0.98 |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Control specification
Control modes | V/F Voltage Vector, Energy Optimised V/F, Sensorless Vector Speed Control, Synchronous Reluctance Motor Control, Brushless DC Motor Control, Open Loop PM Vector Control |
Current/torque limitation | Current limitation |
PWM frquency | 4-32 kHz effective |
Stopping mode | Ramp to Stop: User Adjustable 0.1 – 600 seconds,Coast to Stop |
Braking | Motor Flux Braking |
Skip frequency | No |
Analog setpoint control | 0 to 10V, 10 to 0V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
Digital setpoint control | 4 fixed speeds, Motorised Potentiometer, Keypad, Modbus RTU, CANopen |
Communication
Modbus RTU | 9.6 - 115.2 kbps (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | No |
Modbus TCP | Yes |
Ethernet IP | No |
EtherCat | No |
Profinet IO | No |
Profibus DP(DPV1) | No |
Device Net | No |
CC-Link | No |
CAN open | Yes, 125 - 1000 kbps |
Display
Programmable display | No |
Multi language OLED display | No |
External OLED display | Yes |
LED display | Yes |
HVAC
PID-control | PI-control with sleep/wake up |
Spin start | Yes |
Pump dry protection | No |
Pump prime and burst protection | No |
Stir function | No |
Motor pre-heat | No |
Broken impeller and broken belt detection | No |
Automatic cleaning for pumps | No |
Bypass control | No |
Fire mode | Yes |
Control terminals
Power supply | 100 mA @ 24 VDC, 10 mA @ 10 VDC |
Inputs | 4 in total, 2 Digital, 2 Analog or Digital, selectable |
Digital inputs | 8-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Outputs | 2 total, 1 relay, 1 analog or digital |
Digital transistor outputs | 24VDC/20 mA, Internal supply |
Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 6A AC, 5A DC |
Analog outputs | 0 to 10 V, 10 to 0 V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
Safety inputs | No |
Extra IOs | No |
Control features
Speed control Master/slave | Slave |
Modbus master functionality | No |
Advanced hoist control | No |
Built-in PLC | No |
Standard compliances
Low voltage directive | 2014/35/EU |
EMC directive | 2014/30/EU Cat C1 according to EN61800-3:2004 |
Conformance | CE, UL |
Machine directive | 2006/42/EC |
Marine approvals | No |
Safe torque OFF | No |
Restriction of hazardous substances | RoHS2 |
Registration evaluation and authorisation of chemicals | Reach |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
DC Bus discharge time | EN 61800-5-1:2007 |
Electrostatic discharge | EN 61800-3:2004+A1-2012. Test techniques EN 61000-4-2:2009. |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Electrical fast transient burst | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-4:2004. |
Ambient conditions
Temperature operation | -20 to 40 °C |
Humidity | 95% max, non-condensing |
Maintenance
Fault memory | Last 4 Trips stored with time stamp |
Data logging | Logging of data prior to trip, Current, Temperature, DC Bus Voltage |
Maintenence indicator | No |
Monitoring | Hours Run Meter, kWh/MWh meter |
Resources
Knowledge
- Alarm code running single phase motor with 3-phase output BFI
- 24 VAC connected to terminal 1 will damaged the drive
- Input Phase Loss Detection
- BFI-E3: Digital start signal and Set speed by bus
- Application note BFI-E3, Using The Display Scaling Function
- Application note BFI-E3, Using Standby Mode
- Application note BFI-E3, Setting the Required Stopping Mode
- Application note BFI-E3, Selecting the Start - Restart Mode
- Application note BFI-E3, Programming the Drive User Relays
- Application Note BFI-E3, PI Closed Loop feedback
- Application note BFI-E3, Additional relay output option modules
- Overvoltage levels
- Modbus TCP gateway OPT-3-MTPEG-BFI - Reset IP address to default
- Modbus TCP gateway OPT-3-MTPEG-BFI - Reset IP address to default
- Default network settings OPT-3-MTPEG-BFI and BFI-E3-MTP
- Control of Realy output and Analog/Digital output by Modbus RTU or CAN open
- OLED Remote External Keypad, Working with Multiple Drive Networks
- Analog input BFI-E3
- Single phase motors run by BFI-E3/H3/P2
- Thermal protection inside motor connected to BFI-E3/P2/H3
Drawings
- Cable CAB155: Cable for CANopen between any product and BFI
- Cable CAB154: Cable for CANopen between X2 Control and BFI
- Cable CAB114: Cable for ModBus RS485 between Nexto Xpress and BFI
- Cable CAB113: Cable for ModBus RS485 between X2 panel and BFI
- CAD drawings All BFI-E3 (STEP)
- CAD drawings All BFI-E3 dxf-files
- BFI connection into Modbus RTU or CANopen network
Program examples/Start-up
- Program example iX Developer: Modbus RTU communication between any X2 and BFI-E3, BFI-P2 or BFI-H3.
- Program example CODESYS and iX: X2 Control communication with BFI by Modbus RTU
- Program example BCS Tools and iX: Nexto Xpress communication with BFI by Modbus RTU.
- Program example BCS Tools and iX: Nexto Xpress communication with BFI by CANopen
- Program example CODESYS and iX: X2 Control communication with BFI by CANopen
- Program example CODESYS and iX: X2 control communication with BFI-E3 by Modbus TCP
Configuration files
Software
Manuals
- Start-up document for BFI-E3
- Bedienungsanleitung BFI-E3 (German) Ver1.01
- Manual Modbus RTU 485-communication BFI-E3 (English)
- Manual: User Guide BFI-E3 (English) ver1.20
- Manual CANopen BFI-E3
- Manual BFI-Tools, PC-software for BFI
- Manual BFI-Smartstick for programming by Bluetooth
- Manual for Modbus TCP communication with BFI-E3 from X2 control
Certificates
- Manufacture Declaration for US and Canada
- Manufacture Declaration BFI-E3: CE Declaration of Confirmity
- Conflict Minerals Policy Statement
- Ecodesign for BFI Frequency Inverters
- Modern Slavery Act Company Statement
- RoHS 3, Restriction of Hazardous Substances. September 2021.
- REACH Directive Compliance Statement, January 2023
- Manufacturer declaration: BFI-E3 UKCA Declaration of Conformity
- Manufacturer declaration: UKCA Declaration of Conformity, Options for BFI
- Manufacturer declaration: CE Declaration of Conformity, Options for BFI
Data sheets
- Datasheet: Input AC Line chokes to BFI
- Datasheet: Sine wave filter
- Datasheet: Output chokes for BFI
- Datasheet: External EMC-filters for BFI
- Datasheet Additional relay for BFI-E3, ODP-2ROUT-BFI
- Specification of all BFI, Functions/Hardware
Brochures
Limited availability
BFI-E3-32-0153-1F4A-MTP
Article number 63515-MTP
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: